The ATEX certificate and product label carry the ATEX group and category marking:
II 2 GD
Where:
Signifies compliance with ATEX
II Signifies suitability for use in surface industries
2 Signifies suitability for use in a zone 1 area
G Signifies suitability for use in the presence of gases
D Signifies suitability for use in the presence of dust
Visual Alarm Device – Beacon XB15
Signifies compliance with ATEX
II Signifies suitability for use in surface industries
2 Signifies suitability for use in a zone 1 area
G Signifies suitability for use in the presence of gases
D Signifies suitability for use in the presence of dust
EN54-23:2010 Visual Alarm Device – Beacon XB15
Rating 21.6v- 26.4v DC Absolute. Amps 0.99
Environment Type B Outdoor applications
IP code (IP33C) to BS EN 60529:1992
The Red lens Beacon is supplied with the following CPR and LPCB markings
The White lens Beacon is supplied with the following CPR and LPCB markings
This signifies unit compliance to the relevant European directives, in this case 89/106/EEC, along with the name and
number of the notified body issuing the certificate of conformity.
These units also have the following approvals:
Main Harmonics (AC) to EN61000-6-3:2007 / IEC61000-3-2:2006
Conducted Emissions (DC) to EN61000-6-3:2007
Radiated Field Immunity (DC and AC) to EN61000-6-2:2005 / IEC61000-4-3:2002 + A1:2002
Electrical Fast Transients/Bursts (DC and AC) to EN61000-6-2:2005 / IEC61000-4-4:2004
Surge Immunity (DC and AC) to EN61000-6-2:2005 / IEC61000-4-5:1995 + A1:2000
Dips and Interruptions (AC) to EN61000-6-2:2005 / IEC61000-4-11:2004
Ingress protection (IP66 & 67) to BS EN 60529:92
© MEDC 2015